DATAKOM DSD-080 Seismic Security Panel monitors seismic motions of a strong earthquake and provides relay output signals from it. Output signals are used to shut-off critical installations as natural gas and LPG systems, generators, elevators and the like.
The unit helps reducing damages of a probable earthquake.
On its graphical display screen, the unit shows system status.
DSD-080 incorporates highly sensitive triple axis seismic sensors. The unit is maintenance free and capable of making self-test. The earthquake sensing specifications of DSD-080 conforms to both ANSI Z21.80 (1981), ASCE 25-97 and TS-12884(2002) standards.
DSD-080 operates on mains with a battery backup. 24V/1.2A-h batteries are incorporated to the unit.
The unit provides automatic battery charging feature.
During long mains failures, if batteries get low, the unit gives audible and visible alarm.
Features:
• Conformal to international earhquake standards
• Triple axis motion detection
• Automatic self-test
• Internal 24V battery
• 5 programmable relay outputs (5Amp)
• Wide operating voltage range (85-305VAC)
• Wide operating temperature range (-10...70°C)
TECHNICAL SPECIFICATIONS:
Operating voltage: 85 to 305VAC
Supply power: 4W maximum.
Battery charge voltage: 27.5V (+/-0.2V)
Battery charge current: 100mA maximum
Low battery voltage limit: 22V. (+/- 0.3V)
Current drain from battery: 15mA. max from 24VDC (All relays passive) Additional 6mA for each energized relay.
Battery capacity: 24VDC, 1.2A-h
Operation from battery: >24 hours (typically 72 hours)
Self test: At power-on and reset.
Switching: 5 relay outputs. (5A / 30VDC / 250VAC)
Audible warning: 85dB/1m buzzer.
Operating temperature range: -10 to +70 °C.
Relative humidity: 10% to 90% arası (non-condensing)
Weight: 1900 grams (approximative)
Dimensions: 192x120x65mm (WxHxD)
WE DO NOT SHIP THIS PRODUCT TO USA AND CANADA