DATAKOM: ATS, AMF, AVR, ECM, DKG controllers for diesel, gas, petrol gensets including manual start and auto mains failure generator controls, electronic engine governors, alternator automatic voltage regulators, automatic transfer switches, battery chargers, meters and analyzers, contactors, synchroscopes and automatic synchronizers for multi generating set paralleling and mains synchronization. Buy Datacom online.

DATAKOM DKG-309 MPU Automatic start mains failure control panel for generators (AMF)

Datakom DATAKOM DKG-309 MPU Automatic start mains failure control panel for generators (AMF)
Datakom DATAKOM DKG-309 MPU Automatic start mains failure control panel for generators (AMF)
Datakom DATAKOM DKG-309 MPU Automatic start mains failure control panel for generators (AMF)
(0)
$265.00
pcs.

The Datakom DKG-309 is a comprehensive AMF unit for single genset standby or dual genset mutual standby operations. The unit is available with MPU or CANBUS versions. The CANBUS version connects to ECU controlled electronic engines providing engine control, protection and instrumentation without extra senders. The ECU alarms are displayed in text. The unit is able to initiate modem calls and send SMS messages in fault conditions through external modem.

The unit provides a comprehensive set of digitally adjustable timers, threshold levels, input and output configurations, operating sequences and engine types. All programs may be modified via front panel pushbuttons, and do not require an external unit. Last 100 faults are stored in the event log file. The event log includes not only the date-time information, but also a comprehensive list of measured genset parameters at the time that the fault has occurred. The WINDOWS based RAINBOW program allows remote monitoring and control.

The unit supports MODBUS protocol enabling communication with PLCs and building management systems. The MODBUS protocol is also supported through GSM and PSTN modems. The unit offers multiple language support.

MEASUREMENTS:
Generator Volts: L1-N, L2-N, L3-N
Generator Volts: L1-L2, L2-L3, L3-L1
Generator Amps: L1, L2, L3
Generator KW: L1, L2, L3, total
Generator pf: L1, L2, L3, total
Generator Frequency
Engine rpm
Mains Volts: L1-N, L2-N, L3-N
Mains Volts: L1-L2, L2-L3, L3-L1
Mains Frequency
Battery Voltage
Engine Coolant Temperature
Engine Oil Pressure
Fuel Level
Engine Oil Temperature

DIGITAL INPUTS
The unit has 7 configurable digital inputs. Each input is fully configurable with selectable names, alarm type, polling, latching and contact type.

ANALOG INPUTS
Engine analog inputs are provided for coolant temperature, oil pressure, oil temperature and fuel level. The inputs have programmable sensor characteristics so that they are suitable for any type and brand of sensors.

OUTPUTS
The unit provides 2 relay and 4 semiconductor outputs. 2 of them have programmable functions, selectable from a list. Any function or alarm condition may be a digital output. Using two Relay Expansion Modules, the number of relays may be increased to 22, 16 of them being volt-free contacts.

EVENT LOGGING
The unit records last 100 events with date-time stamp and a total of 18 measured parameters.

TELEMETRY AND REMOTE PROGRAMMING
The unit provides the user with large telemetry facilities via its standard RS-232 serial port, connecting either to a PC, PLC or a GSM or PSTN modem. It supports both RAINBOW and MODBUS communication protocols. The standard PC software offers local and modem operation capabilities as well as modem networking feature.

The PC program is used for below purposes:
- parameter upload/download
- remote monitoring and control
- diagnostics and analysis

The MODBUS interface allows the unit to be integrated in building management systems.

TECHNICAL SPECIFICATIONS:
Alternator voltage: 0 to 300 V-AC (Ph-N)
Alternator frequency: 0-100 Hz.
Mains voltage: 0 to 300 V-AC (Ph-N)
Mains frequency: 0-100 Hz.
DC Supply Range: 9.0 to 33.0 V-DC
Cranking dropouts: survives 0 V for 100ms.
Typical Standby Current: 100 mA-DC
Maximum Operating Current: 200 mA-DC (Relay outputs open)
Generator/Mains Contactor Relay Outputs: 16 A / 250V
DC Outputs: 1A @ 28V protected semiconductor output
Charge excitation: min 2 Watts
Magnetic pickup input:: 0.5 – 30 V-AC.
Magnetic pickup frequency: 10 KHz max.
Current inputs: from CTs, .../5A. Max load 0.7VA per phase.
Analog input range: 0-5000 ohms.
Serial port: RS-232, 9600 bauds, no parity, 1 bit stop
Operating temp.: -20 C (-4 F) to 70 C (158 F).
Storage temp.: -40 C (-40 F) to 80 C (176 F).
Maximum humidity: 95% non-condensing.
Dimensions: 192 x 134 x 46 mm (WxHxD)
Panel Cut-out Dimensions: 151x111 mm minimum.
Weight: 340 g (approx.)
Case Material: High Temperature ABS/PC (UL94-V0)
IP Protection: IP65 from front panel, IP30 from the rear
CE Conformity reference standards:
EN 61010 (safety requirements)
EN 61326 (EMC requirements)
UL / CSA Conformity: certificate # 20110527-E314374
UL 508, Edition 17
UL 2200, 1st Edition.
UL 840 Edition 3
CSA C22.2 NO. 14 - Edition 10


WE DO NOT SHIP THIS PRODUCT TO USA AND CANADA



  • Previous Generation Products
  • 4PRO Contactors and Load Transfer Switches
  • 4PRO Wireless remote control sets
  • Software and Access Licenses
DATAKOM: ATS, AMF, AVR, ECM, DKG controllers for diesel, gas, petrol gensets including manual start and auto mains failure generator controls, electronic engine governors, alternator automatic voltage regulators, automatic transfer switches, battery chargers, meters and analyzers, contactors, synchroscopes and automatic synchronizers for multi generating set paralleling and mains synchronization. Buy Datacom online.