DATAKOM: ATS, AMF, AVR, ECM, DKG controllers for diesel, gas, petrol gensets including manual start and auto mains failure generator controls, electronic engine governors, alternator automatic voltage regulators, automatic transfer switches, battery chargers, meters and analyzers, contactors, synchroscopes and automatic synchronizers for multi generating set paralleling and mains synchronization. Buy Datacom online.

DATAKOM COMM PLUG-IN MODULE with Ethernet,RS-485, USB Host for D-500/700-MK2

Datakom DATAKOM COMM PLUG-IN MODULE with Ethernet,RS-485, USB Host for D-500/700-MK2
(0)
$64.00
pcs.

COMM PLUG-IN MODULE with Ethernet, RS-485 and USB Host

This COMM module is specially designed for Datakom D-500, 700 MK2 controllers.
It includes 3 additional communication interfaces that can be necessary for various purposes.

1.    ETHERNET PORT

Description: IEEE802.3 compliant, 10/100 Base-TX RJ45 Ethernet port with indicating leds
Data rate: 10/100 Mbits/s, auto detecting
Connector: RJ45
Cable type: CAT5 or CAT6
Isolation: 1500 VAC, 1 minute
Max distance: 100m with CAT5 or CAT6 cable
Functionality: Embedded TCP/IP, Web Server, Web Client, SMTP, e-mail, SNMP, Modbus TCP_IP

LED FUNCTIONS:
GREEN: This led turns on when the ethernet link is established (connector inserted)
YELLOW: This led blinks when data transfer occurs inwards or outwards. Periodic blinking will witness data flow.

2.    USB HOST PORT

Description: USB 2.0, not isolated
Power Supply Output: 5V, 300mA max
Data rate: Full Speed 1.5/12 Mbits/s, auto detecting
Connector: USB-A (PC type connector)
Cable length: Max 1.5m
Functionality: USB memory, FAT32, data recording
Memory capacity: All USB flash memories.

The USB-Host port is designed for detailed data recording. The period of recording is adjustable through program parameter.
As soon as a USB flash memory is inserted, the unit will start data recording and continue until the memory is removed.
For more details about data recording please review chapter “Data Recording”.

Warning: If USB-Device is plugged, the USB-Host port will not function.

3.    RS-485 PORT

Connection: 3 wires (A-B-GND). Half duplex.
Baud rate: 2400-115200 bauds, selectable
Data type: 8 bit data, no parity, 1 bit stop
Termination: External 120 ohms required
Isolation: 250VAC, 1 minute
Common mode voltage: -0.5 VDC to +7VDC, internally clamped by transient suppressors.
Max distance: 1200m @ 9600 bauds (with 120 ohms balanced cable)

The RS-485 port features MODBUS-RTU protocol. Multiple modules (up to 128) can be paralleled on the same RS-485 bus for data transfer to automation or building management systems.
The Modbus register list is available upon request.

The RS-485 port provides also a good solution for distant PC connection where RainbowPlus program will enable programming, control and monitoring.
For more details about programming, control and monitoring via RS-485 port, please refer to Rainbow Plus application user manual document.

WE DO NOT SHIP THIS PRODUCT TO USA AND CANADA



  • Previous Generation Products
  • 4PRO Contactors and Load Transfer Switches
  • 4PRO Wireless remote control sets
  • Software and Access Licenses
DATAKOM: ATS, AMF, AVR, ECM, DKG controllers for diesel, gas, petrol gensets including manual start and auto mains failure generator controls, electronic engine governors, alternator automatic voltage regulators, automatic transfer switches, battery chargers, meters and analyzers, contactors, synchroscopes and automatic synchronizers for multi generating set paralleling and mains synchronization. Buy Datacom online.