DATAKOM: ATS, AMF, AVR, ECM, DKG controllers for diesel, gas, petrol gensets including manual start and auto mains failure generator controls, electronic engine governors, alternator automatic voltage regulators, automatic transfer switches, battery chargers, meters and analyzers, contactors, synchroscopes and automatic synchronizers for multi generating set paralleling and mains synchronization. Buy Datacom online.

DATAKOM DKG-119J manual & remote start controller with J1939 Interface

Datakom DATAKOM DKG-119J  manual & remote start controller with J1939 Interface
Datakom DATAKOM DKG-119J  manual & remote start controller with J1939 Interface
Datakom DATAKOM DKG-119J  manual & remote start controller with J1939 Interface
(0)
$186.00
pcs.

The DKG-119 is a comprehensive generator control unit designed to start and stop the generating set both manually and remotely. The manual control is made using the pushbuttons on the front panel. The remote control is made via the REMOTE START input signal.

In AUTOMATIC position, DKG-119 monitors the REMOTE START signal and controls the automatic starting, stopping and load transfer of the generating set. Once the generator is running, it monitors internal protections and external fault inputs. If a fault condition occurs, the unit shuts down the engine automatically and indicates the failure source with the corresponding red led lamp and text.

The DKG-119 provides a comprehensive set of digitally adjustable timers, threshold levels, input and output configurations and operating sequences. All programs may be modified via front panel pushbuttons, and do not require an external unit.

The unit is able to send SMS messages in fault conditions.

The unit offers the magnetic pickup input as standard for engine rpm measurement.

It is possible to monitor and control the operation of the system locally or remotely with the WINDOWS based RAINBOW program (external adapter required).

The unit supports MODBUS protocol enabling communication with PLCs and building management systems.

FEATURES:
• True RMS measurements
• Both manual and remote starting and stopping
• ECU control and monitoring through J1939 CAN
• J1939 ECU warnings displayed as text
• Various engine brands and models available
• Engine control
• Gas engine support
• Engine idle speed control
• Generator protection
• Built in alarms and warnings
• Remote Start operation
• Dual genset mutual standby operation
• Load shedding, dummy load
• Periodic maintenance request indicator
• Event logging with measurements
• Statistical counters
• Field adjustable parameters
• Logic level serial port
• Firmware downloadable from serial port
• Free MS-Windows Remote monitoring SW:
     -monitoring and control
     -download of parameters
     -upload of parameters
• GSM SMS message sending on fault
• MODBUS communications
• Graphic LCD display (128x64 pixels)
• Triple language support
• Customer logo display capability
• Protected semiconductor digital outputs
• Configurable analogue inputs: 3
• Configurable digital inputs: 5
• Configurable relay outputs: 2
• Total relay outputs: 4
• Survives cranking dropouts
• Sealed front panel
• Plug-in connection system for easy replacement

TECHNICAL SPECIFICATIONS:
Alternator voltage: 0 to 300 V-AC Phase to Neutral (0 to 520 V-AC Phase to Phase)
Alternator frequency: 0-100 Hz.
Current input range: 0.1 – 6 A AC
Voltage burden: < 0.1VA per phase
Current burden: < 0.5VA per phase @ 5A AC
Accuracy:
    Voltage: 2.0%+1digit
    Current: 2.0%+1 digit
    Frequency: 0.5%+1 digit
    Power(kW,kVAr): 3.0%+2digit
    Power factor: 3.0%+2digit
DC Supply range: 9.0 VDC to 30.0 VDC
Cranking dropouts: survives 0 V for 100ms
Typical stand-by current consumption: 100 mADC.
Maximum current consumption: 130 mADC.
Digital outputs: 1A @ 28 VDC. Protected semiconductor outputs.
Charge alternator excitation current: min 150 mADC @ 10 to 30 VDC.
Current inputs: from current transformers, .../5A. Max load 0.7VA per phase.
Digital inputs: input voltage 0 - 30 VDC. Internally connected to battery positive via 4700 ohm resistor.
Analog inputs: Resistor input 0 to 5000 ohms connected to the battery negative. Sources 10 mA when closed to battery negative.
Measurement category: CAT III
Air category: Pollution degree II
Communication port: logic levels. 9600 bauds, no parity, 1 stop bit.
Operating temperature range: -20°C to +70°C (-4 ºF to +158°F)
Storage temperature range: -40°C to +80°C (-40 ºF to +176°F)
Maximum humidity: 95%, non-condensing
Dimensions: 96x96x53mm (WxHxD)
Panel Cut-out dimensions: 92x92mm minimum.
Weight: 150 g (approx.)
Case material: High temperature, self extinguishing ABS/PC (UL94-V0)
IP protection: IP65 from front panel, IP30 from the rear


WE DO NOT SHIP THIS PRODUCT TO USA AND CANADA



  • Previous Generation Products
  • 4PRO Contactors and Load Transfer Switches
  • 4PRO Wireless remote control sets
  • Software and Access Licenses
DATAKOM: ATS, AMF, AVR, ECM, DKG controllers for diesel, gas, petrol gensets including manual start and auto mains failure generator controls, electronic engine governors, alternator automatic voltage regulators, automatic transfer switches, battery chargers, meters and analyzers, contactors, synchroscopes and automatic synchronizers for multi generating set paralleling and mains synchronization. Buy Datacom online.