DATAKOM: ATS, AMF, AVR, ECM, DKG controllers for diesel, gas, petrol gensets including manual start and auto mains failure generator controls, electronic engine governors, alternator automatic voltage regulators, automatic transfer switches, battery chargers, meters and analyzers, contactors, synchroscopes and automatic synchronizers for multi generating set paralleling and mains synchronization. Buy Datacom online.

4PRO ATS-125A-4P-rs Automatic Changeover Transfer Switch

Datakom 4PRO ATS-125A-4P-rs  Automatic Changeover Transfer Switch
Datakom 4PRO ATS-125A-4P-rs  Automatic Changeover Transfer Switch
Datakom 4PRO ATS-125A-4P-rs  Automatic Changeover Transfer Switch
(0)
$125.00
pcs.

DESCRIPTION

The ATS-125A-rs changeover switch is designed to automatically transfer load circuits from main power source to reserve source in a wide variety of 1-3 phase applications.

FEATURES

 Electric motor gear activated switching;
 1-3 phase 4 pole operation;
 Auto and Manual mode switch;
 3 position switch handle(”I”-”0”-”II”);
 Generator start/stop remote control outputs;
 High reliability and low power consumption due to fixed positions of the change-over mechanism energized during switching process only;
 Front side position indication pointer and external lamp outputs;
 Control signal protection fuses;
 Built-in mechanical and electrical interlocking.

INPUTS AND OUTPUTS

 Normal source inputs: R, S, T, N;
 Reserve source inputs: R, S, T, N;
 Load cirquit outputs: R, S, T, N;
 External indication lamp outputs.

TECHNICAL SPECIFICATIONS

 Rated Operating Voltage: 230/400V(2-3 phase), 230V (1 phase), 120/208V(3 phase), 120/240V (2 phase).
 Voltage frequency: 50/60Hz.
 Switching poles: 4
 Rated operating current: up to 125А per device pole;
 Working temperature range: от -5'C до +40'C;
 Humidity: up to 95%;
 Installation type: vertical;
 Switching current: up to 0.5A;
 Switching time: 1-2 sec;
 Rated insulation voltage: 800V
 Rated impulse withstand voltage: 8kV
 Rated making capability: 10KA
 Rated short-time withstand currrent Ie 30ms:17KA
 Nominal control supply voltage: 230VAC
 Life switching cycles: up to 10000;
 Use category: AC-331B;
 Altitude: up to 2000 meters;
 Protection class: IP30
 Weight: 2.2 kg.



DATAKOM: ATS, AMF, AVR, ECM, DKG controllers for diesel, gas, petrol gensets including manual start and auto mains failure generator controls, electronic engine governors, alternator automatic voltage regulators, automatic transfer switches, battery chargers, meters and analyzers, contactors, synchroscopes and automatic synchronizers for multi generating set paralleling and mains synchronization. Buy Datacom online.